Resilient floor construction process and technical requirements


Published:

Feb 27,2023

1. Use a thermometer and hygrometer to detect the temperature and humidity. The indoor temperature and the surface temperature should be 15°C, and the construction should not be below 5°C and above 30°C. The relative air humidity suitable for construction should be between 35% and 75%. 2. Use a moisture content tester to detect the moisture content of the base layer, and the moisture content of the base layer should be less than 4%.

1. Use a thermometer and hygrometer to detect the temperature and humidity. The indoor temperature and the surface temperature should be 15°C, and the construction should not be below 5°C and above 30°C. The relative air humidity suitable for construction should be between 35% and 75%.

2. Use a moisture content tester to detect the moisture content of the base layer, and the moisture content of the base layer should be less than 4%.